Ürünler
Ürün ayrıntıları
Ana Sayfa > Ürünler >
Inclosed Emergency Shower and Eyewash With Heating and Chilling System

Inclosed Emergency Shower and Eyewash With Heating and Chilling System

Adedi: 1
Fiyat: $10000
Teslim süresi: 2-3 hafta
Ödeme yöntemi: L/C,D/A,D/P,T/T,Western Union
Tedarik Kapasitesi: 1500L
Detay Bilgisi
Menşe yeri
Çin
Marka adı
Bohua
Sertifika
ANSI Z358.1-2014, CE , ISO
Model numarası
0209-1102
Vurgulamak:

enclosed emergency shower eyewash

,

heated chilled emergency eyewash

,

emergency shower with temperature control

Ürün Açıklaması
Enclosed Emergency Shower and Eyewash With Heating and Chilling System
Product Overview
A comprehensive enclosed emergency safety system featuring integrated heating and chilling capabilities for extreme temperature environments, constructed from high-grade SS316L stainless steel.
Technical Specifications
  • Material: SS316L Stainless Steel
  • Ambient Temperature Range: -45°C to 32°C
  • Water Tank Capacity: ≥1400 liters
  • Inlet Design Conditions: Water pressure 1.2MPA, water temperature 5-8°C
Performance Specifications
Component Water Pressure Outlet Temperature Flow Rate
Emergency Shower 0.18-0.7 MPA 25-35°C ≥100 L/MIN
Eyewash 0.18-0.7 MPA 25-35°C 12 L/MIN
Safety & Control Features
  • Explosion-Proof Components: Electric heater (EXD II CT6 IP66) and position indicator
  • Electrical Specifications: Heater 380V, alarm light 24V
  • Control System: Split explosion-proof box (power box and instrument box)
  • Activation: Eyewash controlled by hand push plate, shower controlled by pull rod
  • Safety Protection: Leakage protection and earth leakage circuit breaker
Additional Features
  • Self-draining eyewash system with DN32 water inlet + ball valve assembly
  • Water inlet with inspection valve and 100 mesh filter
  • Liquid level display and water temperature display in tank
  • DCS signal with passive dry contact and 1/2" gland NPT
  • 2-inch SS316L matching flange ASME B16.5 CL150 & WN-RF for water inlet/outlet
  • Customized SS316L stainless steel nameplate
  • Insulation requirements determined by supplier